Descripción
UT586+ Digital RCD (ELCB) Tester «UNI-T»
| Specification | |||||
| Rate trigger current | Fault trigger time | Accuracy (current) |
Accuracy (time) |
||
| RCD test function | X1/2 | 10/20/30/100/300/500mA/1000mA | 0~2000mS @ 0°/180° | -10%~0%” | ±0.6%rdg±4dgt |
| X1 | 10/20/30/100/300mA | 0~2000mS @ 0°/180° | 0%~+10% | ±0.6%rdg±4dgt | |
| 500mA/1000mA | 0~200mS @ 0°/180° | 0%~+10% | ±0.6%rdg±4dgt | ||
| X2 | 10/20/30/100/200/300/500mA | 0~200mS @ 0°/180° | 0%~+10% | ±0.6%rdg±4dgt | |
| X5 | 10/20/30/100/200mA | 0~200mS @ 0°/180° | 0%~+10% | ±0.6%rdg±4dgt | |
| AUTO | 10/20/30/100/300/500mA/1000mA | 300ms @ 15 0°/180° | -10%~+10% | ±0.6%rdg±4dgt | |
| Manual | 10/20/30/100/300/500mA/1000mA | 300ms @ 0°/180° | -10%~+10% | ±0.6%rdg±4dgt | |
| Working voltage | 50/60Hz | 100V~440V (Note: If > 450V, it will issue an alarm and stop the RCD test) |
-15%~+10% | ||
| Voltage test | Voltage range | 30~480V (Resolution: 1V) | 45~65Hz | ±3%rdg±3dgt | |
| Voltage test | L-PE | yes, display the L-PE input voltage; range: 30V~480V; No input and low voltage: “0V”; if less than 30V: <30V; if more than 4800v: >480V |
|||
| Frequency | yes, display the L-PE input frequency; when it is “volts”, press “VOLT/FREQ” key to switch “Voltage/Frequency” |
||||
| Wiring check | If there is no wiring, an abnormal power supply, or no electricity flowing, the LCD will display “L-PE” and flash. | ||||
| Phase angle selection | You can choose to initiate the test from the positive (0°) or the negative (180°) half-cycle. Press the “0°/180°” button to toggle phase. | ||||
| Lock test | With the power disconnected, press and hold the “0°/180°” button to activate the lock test function. Simply connect the test leads correctly to the test points, and the test will run automatically. | ||||
| AUTO RAMP test | You can test the trip action current and action time simultaneously. | ||||
| RCD test exceeds limit prompt | When the trip action time exceeds the maximum test duration and trips. | ||||
| Over-temperature detection | If the internal components of the device become too hot, the LCD will display an over-temperature symbol, and the device will automatically disable RCD testing. | ||||
| Backlight | Yes, can be turn on/off | ||||
| Low battery indication | yes | ||||
| Auto powwer off | After 5 minutes of no operation, it will automatically shut down. | ||||
| Working environment | 0℃~40℃ | ||||
| Storage environment | -20℃~60℃ | ||||
| Power | 8 * 1.5V AA | ||||
| Polution level | 2 | ||||
| Safety rating | IEC61010-031; IEC61557-1,6; CAT III 600V | ||||